1. Output rated voltage: See table 3
2. Output frequency:0.1Hz、0.05Hz、0.02Hz、0.01Hz
3. Carrying capacity: 0.1Hz max 0.5µF
0.05Hz max 1.1µF
0.02Hz max 2.2µF
0.01Hz max 5.5µF
4. Measurement accuracy:3%
5. Voltage positive, negative peak error:≤3%±3kV
6. Voltage waveform distortion degree:≤5%
7. Conditions of use: indoor, outdoor; temperature:-10℃~+40℃;humidity:≤85%RH
8. Power supply fuse: See table 3
9. Power Supply: Voltage 220V±5%,50/60Hz
Note: If the portable generator is used for power supply, the generator output voltage and frequency are required to be stable (generally, the power is greater than 3kW, the frequency is 50Hz, and the voltage is 220V±5%
10. The electrical capacity of the subject shall not exceed the maximum rated electrical capacity of the instrument, and the value is shown in the table 3;
Model |
Rated voltage |
Carrying capacity |
Power source Safety tube |
Product structure and weight |
30/1.1 |
30kV (Peak value) |
0.1Hz,≤1.1µF |
10A |
Controller:4㎏ Voltage booster:20㎏ |
0.05Hz,≤2.2µF |
||||
0.02Hz,≤4.4µF |
||||
0.01Hz,≤10µF |
||||
40/1.1 |
40kV (Peak value) |
0.1Hz,≤1.1µF |
10A |
Controller:4㎏ Voltage booster:20㎏ |
0.05Hz,≤2.2µF |
||||
0.02Hz,≤4.4µF |
||||
0.01Hz,≤10µF |
||||
50/1.1 |
50kV (Peak value) |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏ Voltage booster:40㎏ |
0.05Hz,≤2.2µF |
||||
0.02Hz,≤4.4µF |
||||
0.01Hz,≤10µF |
||||
60/1.1 |
60kV (Peak value) |
0.1Hz,≤0.5µF |
15A |
Controller:4㎏ Voltage booster:50㎏ |
0.05Hz,≤1.1µF |
||||
0.02Hz,≤2.2µF |
||||
0.01Hz,≤5.5µF |
||||
80/1.1 |
80kV (Peak value) |
0.1Hz,≤0.5µF |
15A |
Controller:4㎏ Voltage booster:50㎏ |
0.05Hz,≤1.1µF |
||||
0.02Hz,≤2.2µF |
||||
0.01Hz,≤5.5µF |
||||
90/1.1 |
90kV (Peak value) |
0.1Hz,≤0.5µF |
15A |
Controller:4㎏ Voltage booster:55㎏ |
0.05Hz,≤1.1µF |
||||
0.02Hz,≤2.2µF |
||||
0.01Hz,≤5.5µF |