1、An overview of the
SF6 Gas Analyzer adopts imported sensors, set SO2, H2S, moisture content and SF6 purity measurement in one, the original multiple instruments to achieve the function of a centralized instrument, greatly saving the gas in the equipment. The instrument has the characteristics of high precision and stable performance.
The instrument adopts color LCD touch screen, Windows operating interface, real-time display of various parameters, fully intelligent operation, massive information storage, built-in rechargeable battery, AC and DC dual use.
2、The main features
Ø Measures humidity (dew point), purity, decomposition (SO2, H2S) into a single device.
Ø Fully imported precision sensor, dew point measurement automatic zero calibration, anti-oil pollution, anti-drift.
Ø Electronic flow display.
Ø Instrument self-diagnosis function, intelligent electric quantity display.
Ø Supports data communication.
Ø Graphic menu.
Ø Measuring range is wide, precision is high and response is rapid.
Ø Is small, intelligent and fully functional.
Ø Has the function of fast data storage, query and print.
Ø Open calibration: The instrument has a calibration function and only needs to be operated on the instrument to complete the calibration.
Ø AC/DC, with a rechargeable lithium battery built in, capable of operating continuously for several hours.
Ø Probe is not affected in condensation, specific pollution, oil and gas and most chemical environments.
3、Technical indicators
SF6 dew point |
Measuring range and accuracy |
Range: -80℃ ~ +20℃ Accuracy: ±1℃ |
The resolution of the |
Dew point 0.1℃ or 1ppm |
|
The response time |
63%[90%] +20~-20℃ Td 5s[45s] -20~-60℃ Td 10s[240s] |
|
SF6 purity |
Measuring range and accuracy |
Range: 0 ~ 100% Accuracy: 0.5% |
The response time |
90%, 30s |
|
SO2 |
Measuring range |
0~100ppm |
precision |
±0.5% |
|
H2S |
Measuring range |
0~100ppm |
precision |
±0.5% |