I.Overview
Transformer DC resistance is a must-test item for semi-finished products, finished products factory test, installation, overhaul, change of tap changer, handover test and preventive test of power sector in transformer manufacturing. It can check the welding quality of the winding joint and whether the winding is short-circuited between turns. It can check whether the contact of each position of the voltage tap changer is good, whether the actual position of the tap changer is consistent with the indicated position, whether the lead wire is broken, and the multi-strand wires are wound in parallel. Whether there is a stock break, etc. In order to meet the needs of fast measurement of transformer DC resistance, our company has developed a hand-held DC resistance tester. The instrument adopts a new power supply technology, which has the characteristics of small size, light weight, large output current, good repeatability, strong anti-interference ability and perfect protection function. The whole machine is controlled by a high-speed single-chip microcomputer, with a high degree of automation, and has the functions of automatic discharge and discharge alarm. The instrument has high test accuracy and simple operation, and can realize fast measurement of transformer direct resistance.
II. Main technical indicators and conditions of use
I.Technical indicators
Test current |
<20mA |
40mA |
200mA |
1A |
3A |
10A |
Measuring range |
100Ω-50KΩ |
1Ω-200Ω |
100mΩ-50Ω |
10mΩ-10Ω |
5mΩ-3Ω |
0.5mΩ~0.2Ω |
Accuracy |
±(0.5%+2) |
±(0.2%+2) |
||||
Minimum resolution |
0.1μΩ |
|||||
Operation method |
Touch screen operation |
|||||
Dimensions |
Host:252*160*65(mm) Outer box:425*335*210(mm) |
|||||
Weight |
Host:2KG Outer box:8KG |
|||||
Battery Specifications |
14.8V 5200mAh |
|||||
Test lead length |
Standard 5 meters, length can be customized |
2.Conditions of Use:
Ambient temperature: 0℃-40℃
Ambient humidity: ≤85%RH
Working power: battery powered